honeywell experion_lx_firmware 关键功能的认证机制缺失
CVE编号
CVE-2022-30317利用情况
暂无补丁情况
N/A披露时间
2022-09-01漏洞描述
Honeywell Experion LX through 2022-05-06 has Missing Authentication for a Critical Function. According to FSCT-2022-0055, there is a Honeywell Experion LX Control Data Access (CDA) EpicMo protocol with unauthenticated functionality issue. The affected components are characterized as: Honeywell Control Data Access (CDA) EpicMo (55565/TCP). The potential impact is: Firmware manipulation, Denial of service. The Honeywell Experion LX Distributed Control System (DCS) utilizes the Control Data Access (CDA) EpicMo protocol (55565/TCP) for device diagnostics and maintenance purposes. This protocol does not have any authentication features, allowing any attacker capable of communicating with the ports in question to invoke (a subset of) desired functionality. There is no authentication functionality on the protocol in question. An attacker capable of invoking the protocols' functionalities could issue firmware download commands potentially allowing for firmware manipulation and reboot devices causing denial of service.解决建议
建议您更新当前系统或软件至最新版,完成漏洞的修复。
参考链接 |
|
---|---|
https://www.cisa.gov/uscert/ics/advisories/icsa-22-242-07 | |
https://www.forescout.com/blog/ |
受影响软件情况
# | 类型 | 厂商 | 产品 | 版本 | 影响面 | ||||
1 | |||||||||
---|---|---|---|---|---|---|---|---|---|
运行在以下环境 | |||||||||
系统 | honeywell | experion_lx_firmware | * | Up to (excluding) r520.1 | |||||
运行在以下环境 | |||||||||
硬件 | honeywell | experion_lx | - | - |
- 攻击路径 网络
- 攻击复杂度 低
- 权限要求 无
- 影响范围 未更改
- 用户交互 无
- 可用性 高
- 保密性 无
- 完整性 高
CWE-ID | 漏洞类型 |
CWE-306 | 关键功能的认证机制缺失 |